Cal Ratings for ARC protective Clothing

What Is the Difference Between ATPV, Ebt and ELIM?

Arc Thermal Performance Value (ATPV) is “the incident energy on a fabric or material that results in sufficient heat transfer through the fabric or material to cause the onset of a second degree burn based on the Stoll curve. The level of protection provided by flame resistant clothing as measured in cal/cm2. An arc rating (ATPV) means that you have a 50% chance of being burned if exposed to an electric arc with the same number of calories of heat. The fabric will usually not break open unless exposed to energy levels higher than the arc rating.

Ebt is similar to ATPV but is determined when break-open occurs before the onset of a second degree burn. Energy breakopen threshold (Ebt) is “the average of the five highest incident energy exposure values below the Stoll curve where specimens do not exhibit breakopen. An arc rating (Ebt) means that the garment will break open if exposed to the same number of calories, but you will not be burned.

All FR fabrics will break-open if exposed to sufficient energy. If an arc rated fabric is exposed to energies higher than its break-open value, the potential for direct skin exposure or non-FR inner layer ignition may result in additional injuries.Important factors influencing a protective systems arc rating (ATPV, Ebt or ELIM) are the fabrics weight, construction, and fibre make-up.

Because PPE Regulation (EU) 2016/425 states that Personal Protective equipment shouldn’t bring any harm to the wearer which conflicts with APTV calculation of a 50% chance of harm to the wearer, therefor ELIM (Energy Limit Value) was created and is calculated by the highest level of energy with a 0% chance of break open or second degree burn.

ATPV, Ebt and ELIM are  evaluated in the same test,  EN61482-1-1 & ASTM F1959 in America , but the first one to be reached is the reported arc rating. While both values (ATPV and Ebt) can be reported, only one arc rating is given to fabric. Only the lowest value will be used on the clothing label.

If an Ebt value is determined and found to be equal or below a determined ATPV value, then the Ebt value is reported as the arc rating and will be noted as “Arc Rating (Ebt)” on the garment label. Ebt fabrics are typically more insulative than they are strong, and generally ATPV fabrics are stronger than they are insulative.

What Is An Arc Flash?

An arc flash is a sudden release of electrical energy that occurs when current jumps across a gap between two conductors or from a conductor to a ground. The arc flash generates an intense burst of heat and light that can cause serious injuries, damage to equipment, and fires.

Arc flashes can occur in a wide range of electrical systems and equipment, including switchgear, transformers, motors, and other high-voltage components. They can be caused by a variety of factors, including equipment failure, human error, or a short circuit.

The intense heat generated by an arc flash can cause severe burns, as well as ignite clothing and other materials in the surrounding area, leading to secondary fires. The bright light from the arc flash can also cause temporary or permanent vision damage.

To prevent arc flash incidents, it’s important to follow proper electrical safety procedures, including wearing appropriate personal protective equipment (PPE), de-energizing equipment before working on it, and maintaining a safe distance from energized equipment.

Understanding Arc Ratings and Calories

Now that you understand FR clothing is tested and given an arc rating, you know that the arc rating measures the amount of heat the flame resistant fabric blocks when exposed to electric arc. The arc rating is the number of calories that the garment is expected to “absorb” if exposed to an electric arc. Arc rating is, in essence, the level of protection provided to you, the wearer.

Calorie is the unit of measure of the heat energy of an arc flash and the protective level of FR clothing. The bigger the calorie number, the greater the heat energy level of arc flash and the greater the protective level of the clothing. You will be protected from an electric arc if your clothing has a higher calorie arc rating than the calories of heat generated by the arc.

While it does not matter if the fabric has an Ebt,  ATPV and or ELIM value, it is important to pay attention to the calorie level the fabric can support* (as expressed in cal/cm2)